Power protection / Voltage stabilisers

Krykard · made by Atandra Energy
Static voltage regulator
Static voltage regulator, 3-phase
15 to 200 kVA
An electronic voltage regulator with no servo motor. It corrects within half a cycle, for sensitive equipment.
- IGBT switching with DSP control
- Corrects within 10 ms
- Manual and automatic static bypass
01 Specification
| Ratings | 15 kVA to 200 kVA - 3 Phase, 4 Wire |
|---|---|
| Nature of Cooling | Air Cooled |
| Control Type | True RMS Sensing and Correction with high speed 20 kHz PWM switching using DSP technology |
| Input Voltage Ranges | SVRT-6060: 360 V - 460 V @ 410 V (LS Series - 15 - 100 kVA; HS Series - 125 - 200 kVA); SVRT-4080: 340 V - 480 V @ 410 V (LS Series 15 - 60 kVA; HS Series - 75 - 125 kVA); SVRT-2080: 320 V - 480V @ 400 V (LS Series 15 - 50 kVA; HS Series - 60 -100 kVA) |
| Output Voltage | 400 V +/-1% for 320 V - 480 V; 410 V +/-1% for 360 V - 460 V & 340 V - 480 V Ranges |
| Voltage Regulation | +/- 1% |
| Efficiency Input Frequency | >98% |
| Input Frequency | 47 Hz to 53 Hz |
| Wave Form | Same as Input |
| Effect of Power Factor | Nil |
| Voltage Sensing Time | < 10 ms (within 1/2 Cycle) |
| Voltage Correction Time | < 10 ms (within 1/2 Cycle) |
| Under/ Over Voltage Cutoff | Electronic cutoff circuit with graded time delay, set @ +5% / -10% of nominal output voltage |
| Overload Cutoff | CT based Electronic cutoff circuit with graded time delay, set @ 110% of rated full load current |
| Short Circuit Protection | MCB/MCCB provided |
| Single Phasing Prevention | Provided |
| Phase Reversal Trip | Provided |
| Transient Protection | Surge Suppressor Type 2 at Input & Spike suppression through MOV at Output are provided |
| Stabiliser Bypass | Manual Bypass is provided; Auto Static Bypass is also provided |
| Emergency Off-Switch | Provided |
| Earth - Neutral High Voltage Trip | Provided |
| Input High Voltage Trip | Optional |
| Resetting Mode | Resetting Mode Manual / Auto option provided with programmable time delay |
| Display Type | 2 Line LCD Panel |
| Parameters Displayed | Input & Output Voltages (Line & Phase); Output Currents & Frequency |
| Event Log | Provided for up to 100 Trip Events |
| Input / Output Terminations | Bolted terminals provided |
| Operating Temperature | 0 to 50 deg Celsius |
| Duty Cycle | Continuous |
| IP Class | IP 20, Indoor Application |
Figures are from Atandra Energy's Krykard Power Conditioners brochure (March 2025). Rows that vary by model in ways the brochure does not state clearly are left out. Please confirm against the current data sheet before ordering; we will send it with the quotation.