Power protection / Online UPS

Krykard · made by Atandra Energy
HX
Industrial online UPS, 3-phase in, 3-phase out
40 to 300 kVA
An industrial three-phase online UPS with a built-in isolation transformer, made for difficult and regenerative loads.
- Nine models from 40 to 300 kVA
- IGBT rectifier and inverter
- Isolation transformer built in
01 Models
| Model | Rated Capacity | Net Weight (kg) |
|---|---|---|
| HX-40 | 40 kVA / 36 kW | 340 |
| HX-60 | 60 kVA / 54 kW | 430 |
| HX-80 | 80 kVA / 72 kW | 580 |
| HX-100 | 100 kVA / 90 kW | 630 |
| HX-120 | 120 kVA / 108 kW | 680 |
| HX-160 | 160 kVA / 144 kW | 790 |
| HX-200 | 200 kVA / 180 kW | 1135 |
| HX-250 | 250 kVA / 225 kW | 1275 |
| HX-300 | 300 kVA / 270 kW | 1355 |
02 Specification
| Input | |
|---|---|
| Input Wiring | Three-phase five-wire (3Φ + N + PE) |
| Rated Voltage | 380 / 400 / 415 Vac |
| Rated Frequency | 50 / 60 Hz |
| Frequency Range | 50 / 60 Hz ± 5 Hz |
| Power factor | ≥ 0.99 |
| Delayed start of Rectifier | 10 s (1 ~ 300 settable) |
| Bypass Voltage Range | ± 20% (settable) |
| Output | |
| Output Wiring | Three-phase five-wire (3Φ + N + PE) |
| Rated Voltage | 380 / 400 / 415 Vac |
| Voltage Regulation | ±1% |
| Frequency | 50 / 60 Hz ± 0.1% in battery mode |
| Waveform | Sinusoidal |
| Crest Factor | 3:1 |
| Total Harmonic Distortion(THDv) | ≤ 2% (linear load); ≤ 5% (non-linear load) |
| Batteries | |
| Charging Current | Charging rate (settable) x battery capacity (settable) x number of battery group (settable) |
| Battery Self-Test | Settable periodic self - test; manually configurable test time and voltage |
| System | |
| Max. no. of Parallel Connections | 6 |
| Protections | Short - circuit, Over load, Over temperature, Battery low voltage, Over voltage, Under voltage, Fan failure |
| Communications | Standard configuration: RS 232, RS 485, Dry contacts Optional configuration: SNMP |
| Display | 7 inches LCD touch screen |
| Others | |
| Operating Temperature | 0° C ~ 40° C |
| Storage Temperature | -25° C ~ 55° C (without battery) |
| Relative Humidity | 0% ~ 95% (non-condensing) |
| Noise level at 1m | ≤ 65 dB |
Figures are from Atandra Energy's Krykard Online UPS brochure (December 2025). Rows that vary by model in ways the brochure does not state clearly are left out. Please confirm against the current data sheet before ordering; we will send it with the quotation.