Power protection / Online UPS

Krykard · made by Atandra Energy
EL / ELB
Online UPS, 1-phase in, 1-phase out
1 to 3 kVA
A small single-phase online UPS for offices, network racks, instruments and medical equipment.
- Online double conversion
- EL has a standard battery; ELB takes extended battery banks
- Tower cabinet
01 Models
| Model | Rated Capacity | Dimensions (W × D × H) (mm) | Net Weight (kg) |
|---|---|---|---|
| EL-01 | 1 kVA / 1kW | 144 x 312 x 216 | 4 |
| EL-03 | 3 kVA / 3 kW | 144 x 417 x 216 | 6.5 |
| ELB-01 | 1 kVA / 900 W | 144 x 317 x 216 | 12.8 |
| ELB-03 | 3 kVA / 2.7 kW | 191 x 419 x 335 | 29.4 |
02 Specification
| Input | |
|---|---|
| Input Wiring | Single - Phase Three - wire (1Φ + N + PE) |
| Rated Voltage | 208 / 220 / 230 / 240 Vac |
| Voltage Range | 110 Vac ~ 176 Vac (linear derating between 50% and 100% load), 176 Vac ~ 280 Vac (no derating), 280 Vac ~ 300 Vac (derating 50%) : 160 Vac ~ 280 Vac 800 W for 1kVA & 2.4 kW for 3 kVA |
| Frequency | 40 / 70 Hz (auto-sensing) |
| Power Factor | > 0.99 |
| Bypass Voltage Range | -25% ~ +15% (settable) |
| Total Harmonic Distortion (THDi) | ≤ 5% |
| Output | |
| Output Wiring | Single - phase Three - wire (1Φ + N + PE) |
| Rated Voltage | 208 / 220 / 230 / 240 Vac (settable via LCD) |
| Voltage Regulation | ±1% |
| Frequency | 45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1% Hz (battery mode) |
| Waveform | Sinusoidal |
| Total Harmonic Distortion (THDv) | ≤ 2% (linear load); ≤ 5% (non-linear load) |
| Crest Factor | 3:1 |
| Overload | 105% - 110% for 30 min, 110% - 130% for 10 min, 130% - 150% for 30s, > 150% for 500 ms |
| Batteries | |
| Recharge Time | Inbuilt Battery model - 90% capacity restored in 3 hours; External Battery model - depends on the battery rating |
| Transfer Time | Mains mode to battery mode: 0 ms Inverter mode to bypass mode: 4 ms (typical) |
| Protections | Short-circuit, Over load, Over temperature, Battery discharge protection, Fan testing protection |
| Communications | RS 232 (standard), USP / RS485 / dry contacts / SNMP (optional) |
| Display | LCD + LED |
| Storage Temperature | -25° C ~ 55° C (without battery) |
| Relative Humidity | 0% ~ 95% (non-condensing) |
| Altitude | ≤ 1000 m; derating 1% for each additional 100 m |
| IP Rating | IP 20 |
| Noise Level at 1m | ≤ 50 dB |
Figures are from Atandra Energy's Krykard Online UPS brochure (December 2025). Rows that vary by model in ways the brochure does not state clearly are left out. Please confirm against the current data sheet before ordering; we will send it with the quotation.
03 Other Krykard ranges