Power protection / Online UPS

Krykard · made by Atandra Energy
EH-33
Online UPS, 3-phase in, 3-phase out
10 to 200 kVA
A three-phase transformerless online UPS, from a 10 kVA cabinet up to 200 kVA.
- Ten models from 10 to 200 kVA
- Transformerless, DSP controlled
- Units can run in parallel
01 Models · 10 to 60 kVA
| Model | Rated Capacity | Net Weight (kg) |
|---|---|---|
| EH-10 | 10 kVA / 10 kW | 31 |
| EH-20 | 20 kVA / 20 kW | 33 |
| EH-30 | 30 kVA / 30 kW | 42 |
| EH-40 | 40 kVA / 40 kW | 42 |
| EH-60 | 60 kVA / 60 kW | 48 |
02 Specification · 10 to 60 kVA
| Input | |
|---|---|
| Input Wiring | Three-phase five wire (3Φ + N + PE) |
| Rated Voltage | 380 / 400 / 415 Vac |
| Voltage Range | 304 - 478 Vac, full load 228V - 304 Vac, load decrease linearly according to the min phase voltage |
| Rated Frequency | 50 / 60 Hz (auto-sensing) |
| Frequency Range | 40 ~ 70 Hz |
| Power Factor | > 0.99 |
| Bypass Voltage Range | Selectable, default -20%- +15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40% |
| Total Harmonic Distortion (THDi) | < 1% (linear load); 3% ( non-linear load) |
| Output | |
| Output Wiring | Three-phase five wire (3Φ + N + PE) |
| Rated Voltage | 380 / 400 / 415 Vac |
| Voltage Regulation | ± 1% ( Iinear load ) |
| Frequency | Synchronized with utility in mains mode, 50 / 60Hz ± 0.1Hz in battery mode |
| Waveform | Sinusoidal |
| Power Factor | 1 |
| Total Harmonic Distortion (THDv) | < 1% (linear load); < 3% (non-linear load) |
| Crest Factor | 3:1 |
| Overload | < 110% for 60 mins, 110% ~ 125% for 10 mins, 125% ~150% for 1 min; > 150%, 200 ms |
| Batteries | |
| DC Voltage | + 240 VDC |
| No. of Batteries | 32 pcs (32 ~ 40 pcs selectable) |
| Recharge Time | 6 - 8 hours depend on the capacity of battery |
| System | |
| Efficiency | Upto 96% Online mode / Upto 98% ECO mode |
| Transfer Time | 0 ms |
| Protections | Short-circuit, Over load, Over Temp, Low Battery, Over Voltage, Under Voltage, Fan Failure |
| Max. no. of Parallel Connections | 4 |
| Communications | Standard configuration: RS232, USB, RS484, NET, dry contacts; Optional configuration; SNMP card, Wi-Fi card, GPRS card |
| Display | 5 inches touch screen |
| Others | |
| Operating Temperature | 0° C ~ 40° C |
| Storage Temperature | - 40° C ~ 70° C |
| Relative Humidity | 0~ 95% (non-condensing) |
| Altitude | < 1000 m, load derated 1 % per 100 m from 1000 ~ 2000 m |
| IP rating | IP 20 |
03 Models · 80 to 200 kVA

| Model | Rated Capacity | Net Weight (kg) |
|---|---|---|
| EH-80 | 80 kVA / 80 kW | 152 |
| EH-100 | 100 kVA / 100 kW | 156 |
| EH-120 | 120 kVA / 120 kW | 160 |
| EH-160 | 160 kVA / 160 kW | 194 |
| EH-200 | 200 kVA / 200kW | 200 |
04 Specification · 80 to 200 kVA
| Input | |
|---|---|
| Input Wiring | Three-phase five-wire (3Φ + N + PE) |
| Rated Voltage | 380 / 400 / 415 Vac |
| Voltage Range | 304 ~ 478 Vac, full load 228 V to 304 VAC, load decrease linearly according to the min phase voltage |
| Rated Frequency | 50 / 60 Hz (auto-sensing) |
| Frequency Range | 40 ~ 70 Hz |
| Power Factor | ≥ 0.99 |
| Bypass Voltage Range | Selectable, default -20% to +15% Up limited: +10%, +15%, +20%, +25%; Down limited: -10%, -15%, -20%, -30%, -40% |
| Total Harmonic Distortion (THDi) | ≤ 3% |
| Output | |
| Output Wiring | Three-phase five wire (3Φ + N + PE) |
| Rated Voltage | 380 / 400 / 415 Vac |
| Voltage Regulation | ±1% (linear load) |
| Frequency | Synchronized with utility in mains mode, 50 / 60Hz ± 0.1 Hz in battery mode |
| Waveform | Sinusoidal |
| Power Factor | 1 |
| Total Harmonic Distortion (THDv) | < 1% (full linear load); < 3% (full non-linear load) |
| Crest Factor | 3:1 |
| Overload | <110 %, 60min; 110% -125%, 10min; 125%-150%, 1min; >150 %, 200ms |
| Batteries | |
| DC Voltage | ± 240 Vdc |
| No. of Batteries | 40 pcs (32 - 40 selectable) |
| Recharge Time | Depends on capacity of battery |
| System | |
| Efficiency | 96% |
| Transfer Time | 0 ms |
| Protections | Short-circuit, Over load, Over Temp, Low Battery, Over Voltage, Under Voltage, Fan Failure |
| Max. no. of Parallel Connections | 4 |
| Communications | Standard configuration: RS232, USB, RS485, NET, dry contacts; Optional configuration: SNMP card, Wi-Fi card, GPRS card |
| Others | |
| Operating Temperature | 0° C ~ 40° C |
| Storage Temperature | -40° C ~ 70° C |
| Relative Humidity | 0% ~ 95% (non-condensing) |
| Altitude | < 1000 m, load derated 1 % per 100m from 1000 to 2000 m |
| IP rating | IP 20 |
| Noise level at 1 m | < 70 dB |
Figures are from Atandra Energy's Krykard Online UPS brochure (December 2025). Rows that vary by model in ways the brochure does not state clearly are left out. Please confirm against the current data sheet before ordering; we will send it with the quotation.