Projects / Case file 01
Three utility loops round a 45 m × 115 m press shop.
A press shop in Chakan asked us to lay out compressed air and cooling water for a new shed and its robot line. This is the drawing we made and what it adds up to.
- Customer
- Press shop, name withheld
- Place
- Chakan, Pune
- Our scope
- Layout drawing and bill of quantities
- Shed
- 45 m × 115 m
- Main pipe, all loops
- 1,087 m

What it shows
Three loops run round the walls of the shed, so every bay can be fed from two directions.
- Blue is compressed air in PPCH 110 mm, pressure class PN10.
- Red is cooling water going in, PPRCT 160 mm PN10.
- Green is cooling water coming back, PPRCT 200 mm PN10.
The cooling tower and three pumps sit 15 m outside the left wall and feed the water loops.
The robot-line zone
On the right, a 15 m × 85 m zone gets its own 110 mm sub-headers for air, water in and water out. Thirteen branch lines leave them, each 15 m long with three or four outlets, and every outlet ends in a 1" valve.
What is left alone
The dashed lines are the existing press machines and their pipework. They are not in our scope; we only tie the new loops into the existing 3" and 4" headers and the new 300T press.
Net lengths from the bill of quantities.
Lengths are read from the drawing and rounded to whole pipes. No wastage is added.
| Line | Pipe | Net length |
|---|---|---|
| Air main, loop and zone sub-header | PPCH 110 mm PN10 | 421 m |
| Air branch lines, 5 × 15 m | PPCH 63 mm PN10 | 75 m |
| Water in, main loop | PPRCT 160 mm PN10 | 327 m |
| Water out, main loop | PPRCT 200 mm PN10 | 339 m |
| Zone water sub-headers, in and out | PPRCT 110 mm PN10 | 230 m |
| Water branch lines, 8 × 15 m | PPRCT 63 mm and 75 mm PN10 | 120 m |
| Outlets, 16 air and 24 water | 32 mm PN16 with 1" valve | 40 outlets |
The full bill of quantities lists every pipe length, coupler, elbow, tee, branch adaptor, valve, flange and clamp with its part number. We prepare one like it for every job we design.
Each service has one colour, on every sheet.
Supply and return never share a colour, so a fitter on a ladder can tell them apart at a glance.
Dashed means existing.
Whatever is already in the plant is drawn dashed and stays out of the quantities.
Whatever we assumed is written down.
Layout drawings are not to scale. Every length or size we had to assume is listed with the bill of quantities, for you to confirm.
Their Unit 2,
installed by TAG.
A 500 m PPCH compressed-air line and a 1,000 m PPRCT cooling-tower water line at Nanekarwadi, Chakan.